| Attribute | Value |
|---|---|
| Model NO. | YH5CX-12 |
| Installation | Fixed |
| Application | AC/DC System |
| Size | Medium |
| Operation Voltage | High Voltage |
| Shape | Cuboid |
| Material | ZnO |
| Brand | Yongde |
| Breaking Capacity | High Voltage Circuit Breakers |
| Arc-Extinguishing Medium | Air |
| Discharge Current | 5kA |
| Voltage | 12kV |
| Transport Package | by Carton |
| Specification | IEC60099-4 |
| Trademark | YongDe |
| Origin | China |
| HS Code | 85354000 |
| Production Capacity | 500,000PCS/Year |
| Type | Nominal System Voltage | Rated Voltage | Minimum Reference Voltage under 1 mA DC | MRV under 1/5 μs Steep Discharge Current | MRV under 8/20 μs Lightning Discharge Current | MRV under 1.2/50μs Impulse Discharge Voltage | Power Frequency Withstand Voltage | 4/10 μs High Current Impulse Twice (kA) | 2ms SW Through-flow Capacity A/18 |
|---|---|---|---|---|---|---|---|---|---|
| YH5CX-13/40 | 10 | 17 | 20 | 46 | 40 | 100 | 26 | 65/80 | 150/250 |
| YH5CX5-17/50 | 10 | 17 | 25 | 57.5 | 50 | 100 | 28 | 85/100 | 250/400 |
| YH5CX5-26/65 | 20 | 26 | 37 | 75 | 65 | 160 | 60 | 85/100 | 250/400 |
| YH5CX-29/73 | 20 | 29 | 41 | 75 | 65 | 160 | 65 | 85/100 | 250/400 |